MICROMASTER

 

MICROMASTER 420
The Universal Inverter for Every Challenge

 

You need a frequency inverter which can be adapted to your individual requirements without any great effort? No problem for our MICROMASTER 420 – the universal inverter for 3-phase networks and optional field-bus connection. Thanks to its modular design, the extensive standard functions can be supplemented with a wide variety of options. And you do not even need tools, as the operator panels and the communications modules can be simply plugged in. Screwless control terminals – as with the rest of the family – make terminal connection child’s play.
 
Typical Uses
 Conveyor systems, material transport, pumps, fans, mechanical engineering.
 
 MICROMASTER 420 – Technical Data

Voltage and power ranges

 

 

200-240 V, ± 10%, 1 AC, 0.12 to 3 kW (0.16 to 4 HP)
200-240 V, ± 10%, 3 AC, 0.12 to 5.5 kW (0.16 to 7.5 HP)
380-480 V, ± 10%, 3 AC, 0.37 to 11 kW (0.5 to 15 HP)

Operating temperature

 

 

-10 °C to +50 °C

Process control

 

 

Internal PI controller

Types of control

 

 

FCC (Flux Current Control), multipoint characteristic (parameterizable V/f characteristic), V/f characteristic

Inputs

 

 

3 digital inputs, 1 analog input

Outputs

 

 

1 analog output, 1 relay output

Link-up to automation

 

 

The ideal partner for your automation needs, from connection to SIMATIC S7-200 to integration in TIA with SIMATIC and SIMOTION.

 


 

MICROMASTER 430
The Specialist for Pumps and Fans

Every task performed by a drive system involves its own specific requirements. There is therefore a demand for inverter solutions that can be easily and flexibly adapted to cope with the broadest variety of challenges. It is exactly this flexibility which characterizes our modular MICROMASTER 430. Specially for use with pumps and fans in industry, it performs a wide variety of tasks in similar applications as well. Compared to the MICROMASTER 420, it features greater power efficiency and has more inputs and outputs as well as an optimized operator panel with switch-over between manual and automatic modes of operation.
 
 Typical Uses
 Specially suitable for pumps and fans.
 
 MICROMASTER 430 – Technical Data

 

Voltage and power ranges

 

380-480 V, ± 10%, 3 AC, 7.5 to 250  kW (10 to 300 HP)

Operating temperature

 

-10 °C to +40 °C

 

Process control

 

Internal PID controller

 

Types of control

 

FCC (Flux Current Control), multipoint characteristic (parameterizable V/f characteristic), V/f characteristic

Inputs

 

6 digital inputs, 2 analog inputs, 1 PTC/KTY input

Outputs

 

2 analog outputs, 3 relay outputs

 

Link-up to automation

 

The ideal partner for your automation needs, from connection to SIMATIC S7-200 to integration in TIA with SIMATIC and SIMOTION.

 


 

MICROMASTER 440
The Powerful All-rounder

Even in the world of drives, there are often forces which are difficult to control. Until the most powerful of our frequency inverters enters the field. The MICROMASTER 440 has been specially designed for those applications which require broader functionality and a greater dynamic response than is usually the case. The sophisticated vector control system ensures a uniformly high drive quality, even when sudden load changes occur. Fast response inputs and positioning deceleration ramps allow movement to target positions even without an encoder. Due to an integrated brake chopper, it works with outstanding precision, even during braking and short declaration ramps. All this is possible within a power range starting at 0.12 kW (0.16 HP) and going up to 250 kW (350 HP).
 
 Typical Uses
 Numerous applications in areas such as material handling systems, the textile industry, elevators, hoisting gear, mechanical engineering and the food, beverages and tobacco industries.
 
 MICROMASTER 440 – Technical Data

 

Voltage and power ranges

 

200-240 V, ± 10%, 1 AC, 0.12 to 3 kW (0.16 to 4 HP)
200-240 V, ± 10%, 0.12 to 45 kW (0.16 to 60 HP)
380-480 V, ± 10%, 0.37 to 250 kW (0.5 to 350 HP)
500-600 V, ± 10%, 0.75 to 90 kW (1.0 to 125 HP)

Operating temperature

 

0.12 to 75 kW (0.16 to 1.0 HP) (CT): -10 °C to +50 °C
90 to 200 kW (125 to 276 HP) (CT): 0 °C to +40 °C

Process control

 

Internal PID controller (autotuning)

Types of control

 

Vector control, FCC (Flux Current Control), multipoint characteristic (parameterizable V/f characteristic), V/f characteristic

 

Inputs

 

6 digital inputs, 2 analog inputs, 1 PTC/KTY input

Outputs

 

2 analog outputs, 3 relay outputs

 

Link-up to automation

 

The ideal partner for your automation needs, from connection to SIMATIC S7-200 to integration in TIA with SIMATIC and SIMOTION.